Governor Model: IEEEG1PID

 

Model Equations and/or Block Diagrams

Parameters:

Droop Droop: Droop setting, pu
Tdc Tdc: Droop Delay, seconds
Kp Kp: Proportional gain, pu
Ki Ki: Integral gain, pu
Kd Kd: Derivative gain, pu
Td Td: Derivative delay, seconds
Tcv Tcv: Valve positioner time constant, sec
Uo Uo: Maximum valve opening velocity, pu/sec
Uc Uc: Maximum valve closing velocity, pu/sec
Pmax Pmax: Maximum valve opening, pu
Pmin Pmin: Minimum valve opening, pu
Pthrot Pthrot: Power Throttle, pu
Tb Tb: High pressure turbine bowl time constant, sec
K1 K1: Fraction of hp shaft power after first boiler pass
K2 K2: Fraction of lp shaft power after first boiler pass
Trh Trh: Reheater time constant, sec
K3 K3: Fraction of hp shaft power after reheater
K4 K4: Fraction of lp shaft power after reheater
Tco Tco: Crossover time constant, sec
K5 K5: Fraction of hp shaft power after crossover
K6 K6: Fraction of lp shaft power after crossover
Trhd Trhd: Double reheat time constant, sec
K7 K7: Fraction of hp shaft power after double reheater
K8 K8: Fraction of lp shaft power after double reheater
Plosshp Plosshp: Power Loss on hp turbine, per unit on hp gen MVABase
Plosslp Plosslp: Power Loss on lp turbine, per unit on lp gen MVABase
Dlim Dlim: Dlim, pu
dbH dbH: Deadband High (pu)
dbL dbL: Deadband Low (pu)
Trate Trate: Model Rating, MW. (If 0, then treated as summation of hp and lp gen MVABase